August, 2005

Firestops and ASTM E-814 (UL 1479)

Polyurethane foam is an organic plastic polymer. Therefore, it is combustible and will burn in the presence of sufficient heat, ignition, etc. With the addition of flame retardants, PU foams can be formulated to pass flame spread tests (i.e. ASTM E-84) which measure their resistance to combustion when exposed to an open flame. However, polyurethane foam is not intended to be used by itself as a fire stop material, according to current accepted U.S. model building codes, such as ICC, NFPA, etc., which specify that through-penetration firestop materials be tested according to ASTM E-814 (UL 1479). In order to pass firestop testing as the sole material being tested (no composite structures), a material must essentially be non-combustible, which is clearly not the case for PU foams.

Recently, several one-component PU foams have created confusion in the marketplace by being marketed with misleading and/or poorly worded claims. These products may create a serious liability risk to the end-user if used improperly, as well as an even more serious potential for the unnecessary loss of life and property in the case of an accidental fire situation. Therefore, the purpose of this Technical Bulletin is to clarify and explain the test requirements for firestop materials. Note that this information is relevant for polyurethane foam in pressurized containers (i.e. aerosols), and is not applicable to "caulk-type" mechanically applied tubes of polyurethane, which may contain other inorganic additives that are not present in pressurized PU foam. In addition, this information does not apply to PU foam for fireblocking, as specifically evaluated by ICC-ES, including testing according to a modified version of ASTM E-814.

ASTM E-814 (UL 1479) is a large scale fire test which evaluates a complete 'through-penetration' assembly for it's ability to withstand exposure to flame, heat and a subsequent water hose stream (to simulate a real-world fire hose situation). Each tested firestop assembly will specify the type of floor or wall that is penetrated (e.g. concrete, steel, framing, etc.), as well as the penetrating item (e.g. metal conduit, plastic pipe, electrical tubing, etc.) and also the fill material (e.g. foam, mineral wool, E 136 fireblock, etc.). Each tested system is assigned an "F Rating" (an hourly rating indicating how long the assembly will withstand the passage of flame, along with a successful hose stream test), a "T Rating" (an hourly rating indicating how long the assembly will prevent a pre-determined temperature rise on the back side of the assembly, along with a successful hose stream test), and sometimes an "L Rating" (air leakage) and a "W Rating" (water leakage). The hourly ratings apply only to the complete system. The individual components are not assigned ratings and are not intended to be interchanged between systems. Additionally, the substitution or elimination of components required in a system should not be made unless specifically permitted.

One-component foam (OCF) that has been tested to ASTM E-814 (UL 1479) requires the additional use of an inorganic material, such as mineral wool, in order to achieve any of the above hourly ratings. Any use of these products in a through-penetration firestop must be done according to an approved system assembly, and with the approval of the Authority Having Jurisdiction (AHJ—in other words, the local building official).

In addition to the U.S. test methods described above, there is also a British Standard (BS 476) test protocol that is used primarily in Europe for evaluating through-penetrations. This test standard does not expose the fill material to the same open flame conditions, or hose stream test, and is therefore not equivalent to the U.S. test.

This information is provided as a service, and is not necessarily meant to reflect any recommendation, guideline or position of Fomo Products, Inc. Each individual user must determine product suitability for any particular purpose.

© 2005-2008 Fomo Products, Inc. All Rights Reserved.
Direct all questions or comments regarding this Web site to our Webmaster.
Please review our Acceptable Use & Privacy Policy,Our Mission Statement and Sitemap.
Powered by: IdeaStar Inc.IdeaStar Inc.